34020201EN/AB - Page 1Galaxy 300010 - 30 kVAMGE UPS SYSTEMSInstallation and usermanualwww.mgeups.comPowerManagementModule250APMMTHEUNINTERRUPTIBLEPOW
Page 10 - 34020201EN/ABPMM1685,5≥ 400 mm1250≥720 mm2. InstallationModule 425 mm deep2. Install the rear base panel 23 (notmandatory).3. Position the
34020201EN/AB - Page 11PMM≥ 400 mm≥720 mm≥720 mm∼ 860 mmBack-to-back assembly2. Installation3. Level the modules using the adjustablefeet 24 .4. Ins
Page 12 - 34020201EN/AB2. InstallationSpecifications for protection devices and cables are provided in section 6 (Appendices, technical data sheet).To
34020201EN/AB - Page 132. InstallationModule without isolationtransformer, combined earth andneutral (TNC system)1. Connect the PEN protection cable
Page 14 - 34020201EN/ABQ2Q112345612332. Installation2.3 Output circuit connections2.4 Alarm and remote shutdown connections1. Connect the NO remote sh
34020201EN/AB - Page 15Q2Q1RS-232RS-4851232. Installation2.5 Communication connections1. Connect the communication cable to theRS232 or RS485 connect
Page 16 - 34020201EN/AB3. Operation3.1 Turning on the PMM module1. Close the upstream switching device (external and not supplied) on the circuit supp
34020201EN/AB - Page 17GENE KWH 0000.0MCM KW 0000.0Ph-A CH01 0.000BCM CH02 0.0003. Operation3.4 AlarmsAlarm text:WARNI
Page 18 - 34020201EN/AB3. Operation3.5 SetupCommunication settingsSettings include:◗ Routing Address (ON, OFF): internal setting reserved for MGE UPS
34020201EN/AB - Page 194. Maintenance4.1 Trouble-shooting and solutionsAlarmWARNINGALARMOVER VOLTAGEOVER CURRENTAUX INPUT ALARMMeaningThe current on
Page 2 - 34020201EN/AB
Page 20 - 34020201EN/AB5. EnvironmentThis product has been designed to respect the environment.It does not contain CFCs or HCFCs.Recycling at the end
34020201EN/AB - Page 216. Appendices6.1 Technical data sheetsElectrical characteristicsRated input current: 250 A per phase and 400 A for the neutral
Page 22 - 34020201EN/ABMXF2Q2F1MXF2Q1 Q2F16. Appendices6.2 Simplified diagramsVersion with isolation transformerVersion without isolation transformerC
34020201EN/AB - Page 236. Appendices6.3 Auxiliary contact functionsNormal operationDowngraded operationOverload or overvoltageOther faultType 2-alarm
Page 24 - 34020201EN/AB6. AppendicesThese bits go to 1 when the current in acorresponding output circuit is greater thanthe minor alarm threshold (60%
34020201EN/AB - Page 256. Appendices# Bit R/W NV Description47 R/W NV Major alarms on circuits 1 to 160 Current in circuit 01 > 80%1 Current in ci
Page 26 - 34020201EN/AB6. Appendices# Bit R/W NV Description69 R/W NV Rating of breaker on circuit 1870 R/W NV Rating of breaker on circuit 1971 R/W N
34020201EN/AB - Page 276. Appendices# Bit R/W NV Description136 R/W NV Major alarm threshold (%) for circuit 01137 R/W NV Major alarm threshold (%) f
Page 28 - 34020201EN/AB6. Appendices# Bit R/W NV Description202 R/W NV Minor alarm delay for circuit 25203 R/W NV Minor alarm delay for circuit 26204
34020201EN/AB - Page 29# Bit R/W NV Description268 W Global circuit breaker rating269 W Global minor alarm threshold (%)270 W Global major alarm thre
34020201EN/AB - Page 3IntroductionThank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment.The Power Management Module
Page 30 - 34020201EN/AB6. Appendices# Bit R/W NV Description12 Current in circuit 13 > 80%13 Current in circuit 14 > 80%14 Current in circuit 15
34020201EN/AB - Page 31Card MCM (general status and measurements)# Bit Float. R/W NV Coeff. Description1 257/258 R/W NV 0.1 Energy consumed in kWh (l
Page 32 - 34020201EN/AB6. Appendices6.5 GlossaryALARM Major alarm signalling that the current in the output circuit considered is higher than 80%of it
34020201EN/AB - Page 336. Appendices6.5 IndexAAlarmsDisplayed ... 17, 19Remote ...
Page 34 - 34020201EN/AB
Page 4 - 34020201EN/ABStructure of this documentMandatory instructionsGeneral instructions, advice, helpIndicationActionSymbolsInformation may be foun
34020201EN/AB - Page 5Contents1. Presentation1.1 250 A PMM modules ...
Page 6 - 34020201EN/AB1. Presentation1.1 250 A PMM modulesHeightin mm190019001900190019001900Module characteristicsWidthin mm121512151215121512151215D
34020201EN/AB - Page 7A-01A-03A-05A-07A-09A-11A-13A-15A-17A-19I 0 I 0 I 0I 0 I 0 I 0Q1Q2B-01B-03B-05B-07B-09B-11B-13B-15B-17B-19C-01C-03C-05C-0
Page 8 - 34020201EN/ABQ2Q1MGE UPS SYSTEMSCRITICAL POWER MONITORING SYSTEMDOWNUP SELECT METERNEXTPARAMETERPREVIOUSPARAMETERHOLDREADINGSCROLLMETERSSETUP
34020201EN/AB - Page 9PMM≥720 mm≥400 mm2. Installation2.1 Setting up the moduleModule 825 mm deep1. Install the lower base panels 23 on thesides th