Type VCP-W Vacuum Circuit Breakers
ANSI 5/15 kV at 1200-3000 Amperes
250-1500 MVA, 60-95 kV BIL
IEC 3.6/17.5 kV at 630-2000 Amperes
25-40 kA, 40-95 kV BIL
The leading value-added modular
approach for assembling metal-clad
switchgear featuring Cutler-Hammer
medium voltage vacuum circuit
breakers, structures and accessories.
The World’s Most Complete
Line of Medium Voltage
Vacuum Circuit Breakers
Breaker Type Voltage Class Insulation BIL Interrupting Ratings Continuous Current Application
VCPW-ND ANSI 5 kV 60 kV 250 MVA 1200A 26" Wide New Metal-Clad Switchgear
IEC 3.6-7.2 kV 40-60 kV 25-31.5 kA 630-1250A
or Upgrades to Existing Airbreak Switchgear
VCP-W ANSI 5-15 kV 60-95 kV 250-1500 MVA 1200-3000A 36" Wide New Metal-Clad Switchgear
IEC 3.6-17.5 kV 40-95 kV 25-40 kA 630-2000A
or Upgrades to Existing Switchgear
VCPW-SE ANSI 5-15 kV 60-95 kV 250-1500 MVA 1200-3000A 36" Wide Special Environment Metal-Clad
IEC 3.6-17.5 kV 40-95 kV 25-40 kA 630-2000A
Switchgear Featuring Breakers with Cycloaliphatic
Epoxy Insulation for Harsh Industrial Environments
VCP-W ANSI 27 kV 125 kV 16-40 kA 600-2000A 36" Wide Metal-Clad Switchgear
IEC 24 kV 125 kV 16-25 kA 630-2000A
or Upgrades to Existing Switchgear
VCP-W ANSI 38 kV 170 kV 16-40 kA, 600-2500A 42" Wide Metal-Clad Switchgear
1500 MVA
VCP-W (Outdoor) ANSI 15.5 kV 110 kV 16-31.5 kA 600-1200A Outdoor Station Distribution Breakers
W-VAC IEC 3.6-17.5 kV 40-95 kV 16-40 kA 630-2000A 600-750 mm Wide IEC Medium Voltage Switchgear
W-VAC IEC 3.6-17.5 kV 40-95 kV 31.5-50 kA 2500-3150A 1000 mm Wide IEC Medium Voltage Switchgear
W-VAC IEC 36 kV 170 kV 16-31.5 kA 630-2000A 42" Wide IEC Metal-Clad Switchgear
DHP-VR ANSI 5-15 kV 60-95 kV 250-1000 MVA 1200-3000A DHP Metal-Clad Switchgear Technology Upgrades
with the DHP-VR Direct Roll-in Vacuum Replace-
ment Breakers from the Original Manufacturer
VCP-WR ANSI 5-15 kV 60-95 kV 250-1500 MVA 1200-3000A Modular Fixed Vacuum Circuit Breakers in 18", 20",
and 29" Widths for Conversions/Retrofits, Metal
Enclosed Switchgear and Mining Switchgear
VCP-WC ANSI 5-17.5kV 95kV 25-63kA 1200-3000A 36" wide Metal-Clad Switchgear
VCP-WG ANSI 5-15kV 95kV 50-63kA 1200-3000A 36" wide Metal-Clad Switchgear
VCP-T ANSI 5-15kV 95kV 16-25kA 800-1200A Smaller frame breaker
VCP-TR IEC 3.6-17.5kV 95kV 16-25kA 630-1250A Smaller frame breaker
Series 18, 20, and 29
MEDIUM VOLTAGE VACUUM
CIRCUIT BREAKERS
Eaton Corporation
Cutler-Hammer business unit
1000 Cherrington Parkway
Moon Township, PA 15108
United States
tel: 1-800-525-2000
www.cutler-hammer.com
© 2003 EATON CORPORATION
ALL RIGHTS RESERVED
PRINTED IN USA
FORM NO. BR01301006E
SEPTEMBER 2003
OEM
SWITCHGEAR
COMPONENT
PRODUCTS
Zobrazit stránku 0
1 2 3 4 5 6 ... 166 167

Shrnutí obsahu

Strany 1 - CIRCUIT BREAKERS

Type VCP-W Vacuum Circuit BreakersANSI 5/15 kV at 1200-3000 Amperes250-1500 MVA, 60-95 kV BILIEC 3.6/17.5 kV at 630-2000 Amperes25-40 kA, 40-95 kV BIL

Strany 2

Cutler-Hammer ProductsCutler-Hammer 5/15 kV Medium Voltage Switchgear ComponentsUL Recognized6No More than You Want…No Less than You Need7A Modular Va

Strany 3

Power-Zone® 4Technical Overview6511/2005© 2005 Schneider Electric All Rights ReservedHigh Resistance Grounded SystemsWhen continuance of service for a

Strany 4

66© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Technical OverviewDelta Systems ConfiguredA neutral point must be established in

Strany 5

Power-Zone® 4Technical Overview6711/2005© 2005 Schneider Electric All Rights ReservedAutomatic Transfer SystemsAutomatic transfer systems minimize pow

Strany 6

68© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Technical OverviewMain-Tie-Main Circuit BreakersBoth main circuit breakers, conne

Strany 7

Power-Zone® 4Wiring Diagrams6911/2005© 2005 Schneider Electric All Rights ReservedSECTION 4 : WIRING DIAGRAMSSECTION CONTENTS “Basic Electrically Oper

Strany 8

70© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Wiring DiagramsBASIC ELECTRICALLY OPERATED CIRCUIT BREAKER DIAGRAMSThis section c

Strany 9

Power-Zone® 4Wiring Diagrams7111/2005© 2005 Schneider Electric All Rights ReservedFigure 45: Masterpact NT Alarm and Cradle Contacts NW/NT Circuit Bre

Strany 10 - Cutler-Hammer Products

72© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Wiring DiagramsMasterpact NW/NT Power, Trip Unit, and Remote OperationFigure 46:

Strany 11

Power-Zone® 4Wiring Diagrams7311/2005© 2005 Schneider Electric All Rights ReservedFigure 47: Masterpact NT Power, Trip Unit, and Remote Operation T4T3

Strany 12

74© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Wiring DiagramsNW/NT Circuit Breaker Trip Units and Remote OperationNOTE: When ne

Strany 13 - Vacuum circuit breaker

Cutler-Hammer ProductsCutler-Hammer 5/15 kV Medium Voltage Switchgear ComponentsUL Recognized6No More than You Want…No Less than You Need7A Modular Va

Strany 14 - [ Circuit breakers ] HVX

Power-Zone® 4Dimensions7511/2005© 2005 Schneider Electric All Rights ReservedSECTION 5 : DIMENSIONSSECTION CONTENTS“Top and Bottom Conduit Entrance La

Strany 15 - Switchboards

76© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 DimensionsTOP AND BOTTOM CONDUIT ENTRANCE LAYOUTSFigure 48: Top and Bottom Condui

Strany 16 - Service Entrance Switchboards

Power-Zone® 4Dimensions7711/2005© 2005 Schneider Electric All Rights ReservedFigure 49: Top and Bottom Conduit Entrance Dimensions (30-inch wide)–Not

Strany 17 - 60-800 Series

78© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 DimensionsFigure 50: Top and Bottom Conduit Entrance Dimensions (36-inch wide)–No

Strany 18 - 60-100 Series

Power-Zone® 4Dimensions7911/2005© 2005 Schneider Electric All Rights ReservedFigure 51: Top and Bottom Conduit Entrance Dimensions (22-inch wide Main,

Strany 19

80© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 DimensionsFigure 52: Top and Bottom Conduit Entrance Dimensions (30-inch wide Mai

Strany 20 - 60-400 Series

Power-Zone® 4Dimensions8111/2005© 2005 Schneider Electric All Rights ReservedFigure 53: Top and Bottom Conduit Entrance Dimensions (36-inch wide Main,

Strany 21

82© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 DimensionsFigure 54: NEMA 3R Walk-in Low Voltage Switchboard/Switchgear Top Condu

Strany 22

Power-Zone® 4Dimensions8311/2005© 2005 Schneider Electric All Rights ReservedFigure 56: Front Elevation Dimensions–Not for Construction (consult facto

Strany 23

84© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 DimensionsFigure 57: Front Elevation Dimensions–Not for Construction (consult fac

Strany 24

Type VCP-W Vacuum Circuit BreakersANSI 5/15 kV at 1200-3000 Amperes250-1500 MVA, 60-95 kV BILIEC 3.6/17.5 kV at 630-2000 Amperes25-40 kA, 40-95 kV BIL

Strany 25

Power-Zone® 4Dimensions8511/2005© 2005 Schneider Electric All Rights ReservedFigure 58: Front Elevation Dimensions–Not for Construction (consult facto

Strany 26

86© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 DimensionsFigure 59: Front Elevation Dimensions–Not for Construction (consult fac

Strany 27

Power-Zone® 4Dimensions8711/2005© 2005 Schneider Electric All Rights ReservedFigure 61: Right Side View, NEMA 3R Walk-in Low Voltage Switchboard/Switc

Strany 28

88© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 DimensionsSYSTEM DESIGNFigure 62: Front Elevation Dimensions–Not for Construction

Strany 29

Power-Zone® 4Dimensions8911/2005© 2005 Schneider Electric All Rights ReservedFigure 63: Front Elevation Dimensions–Not for Construction (consult facto

Strany 30

90© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 DimensionsWEIGHTSRefer to the shipping documents for the correct weights and dime

Strany 31

Power-Zone® 4Suggested Specifications9111/2005© 2005 Schneider Electric All Rights ReservedSECTION 6 : SUGGESTED SPECIFICATIONSSECTION CONTENTS“Genera

Strany 32

92© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Suggested SpecificationsGENERALThis specification and associated drawings describ

Strany 33

Power-Zone® 4Suggested Specifications9311/2005© 2005 Schneider Electric All Rights ReservedAvailable short-circuit current ratings are outlined below.

Strany 34

94© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Suggested SpecificationsMasterpact NW and NT Circuit BreakersA. Each circuit brea

Strany 35

[ Circuit breakers ]1HVXWhether you are planning new switchgear installations or upgrading existing ones, you need cost-effective and reliable compone

Strany 36

Power-Zone® 4Suggested Specifications9511/2005© 2005 Schneider Electric All Rights ReservedCable Compartment A. All incoming or outgoing power conduct

Strany 37

96© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Suggested SpecificationsTable Values:– Not ApplicableX Standard FeatureO Optio

Strany 38 - TABLE OF CONTENTS

Power-Zone® 49711/2005© 2005 Schneider Electric All Rights ReservedAaccessory terminals 17applicationcircuit breaker 7–8seismic 8voltage systems 9

Strany 39

98© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 through-the-door construction 23typical assembly 13system design3 bay representa

Strany 40

Power-Zone® 49911/2005© 2005 Schneider Electric All Rights Reserved

Strany 41

6037CT9901R4/05 © 2005 Schneider Electric All Rights Reserved Replaces 6037CT9901R9/02Schneider Electric USA8821 Garners Ferry RoadColumbia, SC 29209

Strany 42

Gain energy insight andcontrol with PowerLogic™PowerLogic ION7300 seriespower and energy meter

Strany 43

Features Measurements Bidirectional, absolute, and net energy measurements. Rolling block, predicted, and thermal demand. Individual and total harmon

Strany 44

PowerLogic ION7300 series Schneider Electric PowerLogic ION7300 series meters offer unmatched value, functionality, and ease of use. Used in enterpris

Strany 45

InstallationStandard PowerLogic ION7300 series meters with integrated display are designed to fit into DIN standard 92 X 92 mm (3.62 x 3.62 in.) cutout

Strany 46

[ Circuit breakers ] HVX205/2010Greater flexibilityHVX is available in a range of standard, fixed or withdrawable configurations, with plug-in or bolt

Strany 47

Example meter display formats.Power and energy measurementsFully bi-directional, 4-quadrant, revenue-accurate or revenue-certified energy metering. The

Strany 48

Data and event logging (ION7330, ION7350)Ships with a comprehensive data-logging configuration. Data is prioritised and stored onboard in nonvolatile

Strany 49

General specificationsEtherGate and ModemGate The meters can provide gateway functionality depending on communication options. EtherGate: provides acc

Strany 50

1 ION7330 and ION7350 models onlyDIGITALPOWERMETER20SJThe 2007 award recognizes Schneider Electric for its technological advancements and wide produc

Strany 52

1The ASCO 7000 Se rie s Closed-Transition Soft Load Power Transfer Switch gives you the flexibility to:• Satisfy a broad range of power applications

Strany 53

The ASCO 7000 Seri e s Soft Load Power Transfer Switch:• Seamlessly transfers loads between acceptable utility power and onsite genera-tion with virt

Strany 54

The ASCO 7000 Seri es Soft Load Power Transfer Switch synchronizes and parallels two independent power sources, without interrupting power flow

Strany 55

EC ComInterfaceEngineControlGov.VRNetworkDeviceDSL orCable ModemPower Manager XPSoft Load Controller7000 SERIESCTTS Controllerinternal communicationse

Strany 56

ASCO power transfer switch-es—the standard of the indus-try—synchronize and parallel generation and utility power, allowing critical load transfers wi

Strany 57

Switchboards1199 ‡For prices refer to List Price Book K-1KSwitchboardsOrdering Information1. Order main and distribution sections from pages 3-7.60-80

Strany 58

The ASCO 7000 Seri es Closed-Transition Soft Load Power Transfer Switch with bypass-isolation switch-ing allows the switch to be inspected, tested and

Strany 59

Advanced Power Control and MonitoringTwo Power Managers, one each dedicated to utility and onsite power sources, provide protective relay functions fo

Strany 60

Control InterfacesThe Controller—the most advanced digital controller in the industry—automatically starts the engine and controls load transfer to an

Strany 61

The intuitive, touch-screen GUI (graphical user interface) Panel displays at-a-glance operational status and enables users to set, monitor and con-tro

Strany 62

7000 Series Source Summary Screen A screen for each power source shows detailed displays of a variety of electrical parameters:• Phase voltages and

Strany 63

Closed-Transition Soft Load Transfer Switch The sample catalog number below is 7ASLSA3400N5CTo order an ASCO 7000 Series Closed-Transition Soft L

Strany 64

Switch Rating Max. # of Conductors Range of AL-CU Amps per Terminal Conductor Sizes 150, 260, 400 One #4 AWG to 600 MCM 600 Two #1/0 AWG

Strany 65

Switch Rating Poles Width Height Depth amps inches (mm) inches (mm) inches (mm)Enclosed UL Type 1 (Consult ASCO for Type 3R dimensions.)

Strany 66

Switch Rating Poles Type 1* amps Enclosure 150, 260, 400, 600 3 1140 (518) 150, 260, 400, 600 3 with B 1200 (545) 800, 1000, 1200 3 16

Strany 67

Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2010 Emerson Electric Co. Publicat

Strany 68

SwitchboardsK-2 ‡For prices refer to List Price Book 1199KSwitchboardsService Entrance SwitchboardsService Entrance Switchboards typically comprise th

Strany 69

THE UNINTERRUPTIBLE POWER PROVIDERwww.mgeups.comAfter considerable success worldwide, MGE is pleased to introduce the Galaxy PW for the North American

Strany 70

U-Talk cardRS232/RS485 serial cardUSBSNMP or XML Web cardDry Contact Relay cardA back-lit, wide-angle graphic display lets you scrollthrough clear mes

Strany 71

Energy Efficiency – Cost Savings that MattersA major factor in selecting a high-power UPS is its efficiency. The reason is simple, an efficiency adva

Strany 72

UPS Module Specifications 100 kVA 130 kVA 150 kVAInput Voltage (V) 208 480 480 600 208 480 480 600 208 480 480 600Output Voltage (V) 208 208 480 600 2

Strany 77

Switchboards1199 ‡For prices refer to List Price Book K-3KSwitchboards60-800 Series(Maximum 600 Volts, 1200 Amps)Features• 1200A maximum bus design• A

Strany 78

SwitchboardsK-4 ‡For prices refer to List Price Book 1199KSwitchboards60-100 Series(Maximum 600 Volts, 1200 Amps)Features• 1200A maximum bus design• A

Strany 79

Switchboards1199 ‡For prices refer to List Price Book K-5KSwitchboardsDimensional Information60-100 Main CellBusless wireway width (ww) is 16”, bussed

Strany 80

Cutler-Hammer ProductsCutler-Hammer 5/15 kV Medium Voltage Switchgear Components2 11VacClad-W, the Cutler-Hammer vacuumswitchgear family, has been eng

Strany 81

SwitchboardsK-6 ‡For prices refer to List Price Book 1199KSwitchboards60-400 Series(Maximum 600 volts, 6000 Amps)Features• 6000A maximum bus design• A

Strany 82

Switchboards1199 ‡For prices refer to List Price Book K-7KSwitchboards60-400 Main CellDimensional InformationMain Cell Dimensions (in)Amps Main Device

Strany 83

SwitchboardsK-8 ‡For prices refer to List Price Book 1199KSwitchboards1Moulded Case Circuit BreakersNote:1. CJL and CJM breakers have optional electro

Strany 84

Switchboards1199 ‡For prices refer to List Price Book K-9KSwitchboardsMoulded Case Circuit BreakersFusible SwitchesNote:1. For fuses see Section E.60-

Strany 85

SwitchboardsK-10 ‡For prices refer to List Price Book 1199KSwitchboardsMoulded Case Circuit BreakersInterrupting CapacityNote:1. Bolt-Loc and Power-Lo

Strany 86

Switchboards1199 ‡For prices refer to List Price Book K-11KSwitchboardsFor CJL, CJM, CMH and CK accessories, see section I.(1200A QMQB Only)tAccessory

Strany 87

SwitchboardsK-12 ‡For prices refer to List Price Book 1199KSwitchboardsNNotes:1. CJL and CJM are available with optional electronic trips (with suffix

Strany 88

Switchboards1199 ‡For prices refer to List Price Book K-13KSwitchboardsNNotes:1. CK breakers have electronic trips only.2. CJL and CJM are available w

Strany 89

SwitchboardsK-14 ‡For prices refer to List Price Book 1199KSwitchboardsNotes: 1. Above prices include mounting hardware and installation.2. Twin pole

Strany 90

Switchboards1199 ‡For prices refer to List Price Book K-15KSwitchboardsFederal Pioneer Switchboards accept NB type branch circuit breakers. Two metho

Strany 91

Cutler-Hammer ProductsCutler-Hammer 5/15 kV Medium Voltage Switchgear Components2 11VacClad-W, the Cutler-Hammer vacuumswitchgear family, has been eng

Strany 92

SwitchboardsK-16 ‡For prices refer to List Price Book 1199KSwitchboards• Available in 60-100 and 60-400 only.• NBDP interior is mounted directly on sw

Strany 93

Switchboards1199 ‡For prices refer to List Price Book K-17KSwitchboardsNote: 1.15A and 20A 1 pole NB Breakers are switching duty rated.Notes:1. 10 kA

Strany 94

SwitchboardsK-18 ‡For prices refer to List Price Book 1199KSwitchboardsPoles Amps Cat. No. List Price ‡260 NB260NA70 NB270NA100 NB2P100NA360 NB3P60NA

Strany 95

Switchboards1199 ‡For prices refer to List Price Book K-19KSwitchboardsNote:1. Includes PMD-32 display monitorPowerLogic• Disturbance Monitoring• True

Strany 96

SwitchboardsK-20 ‡For prices refer to List Price Book 1199KSwitchboardsMetering Locations

Strany 97

Switchboards1199 ‡For prices refer to List Price Book K-21KSwitchboardsSwitchboard OptionsNote: 1. Cu Bus standard on 4000/5000A 60-400Description Swi

Strany 98

Class 6037Power-Zone® 4Low Voltage, Metal-Enclosed, Drawout Switchgear with Masterpact® NW and NT Low Voltage Power Circuit BreakersCatalog05CONTENTSD

Strany 100 - Power-Zone

Power-Zone® 4Table of Contents311/2005© 2005 Schneider Electric All Rights ReservedTABLE OF CONTENTSTABLE OF CONTENTS...

Strany 101 - Technical Overview

4© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Table of ContentsTop and Bottom Conduit Entrance Layouts ...

Strany 102

Cutler-Hammer ProductsCutler-Hammer 5/15 kV Medium Voltage Switchgear ComponentsInterrupterStemContactSegmentsDrivingForceon theColumnarArcArcCurrentP

Strany 103

Power-Zone® 4Product Description511/2005© 2005 Schneider Electric All Rights ReservedSECTION 1 : PRODUCT DESCRIPTIONSECTION CONTENTS“Introduction” .

Strany 104 - SECTION 4 : WIRING DIAGRAMS

6© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Product DescriptionINTRODUCTION Power-Zone® 4 low voltage, metal-enclosed, drawout

Strany 105

Power-Zone® 4Product Description711/2005© 2005 Schneider Electric All Rights ReservedCompartmentalizationStructures are compartmentalized and are buil

Strany 106

8© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Product DescriptionDisconnecting ContactsThe main disconnecting contacts (power pl

Strany 107

Power-Zone® 4Product Description911/2005© 2005 Schneider Electric All Rights ReservedEquipment RatingsApplication Voltage Systems Ampacities600 Vac Ma

Strany 108

10© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Product Description

Strany 109

Power-Zone® 4General and Application Information1111/2005© 2005 Schneider Electric All Rights ReservedSECTION 2 : GENERAL AND APPLICATION INFORMATIONS

Strany 110 - SECTION 5 : DIMENSIONS

12© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 General and Application InformationINTRODUCTIONPower-Zone® 4 switchgear with Mast

Strany 111 - Dimensions

Power-Zone® 4General and Application Information1311/2005© 2005 Schneider Electric All Rights ReservedSTRUCTUREThe switchgear assembly is composed of

Strany 112

14© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 General and Application InformationThe examples below depict a typical Power-Zone

Strany 113

Cutler-Hammer ProductsCutler-Hammer 5/15 kV Medium Voltage Switchgear ComponentsInterrupterStemContactSegmentsDrivingForceon theColumnarArcArcCurrentP

Strany 114

Power-Zone® 4General and Application Information1511/2005© 2005 Schneider Electric All Rights ReservedENCLOSURESNEMA Type 1 Indoor EnclosuresThe stand

Strany 115

16© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 General and Application InformationNEMA Type 3R Walk-In EnclosuresPower-Zone 4 sw

Strany 116

Power-Zone® 4General and Application Information1711/2005© 2005 Schneider Electric All Rights ReservedControl and Communications WiringFigure 6: Condu

Strany 117

18© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 General and Application InformationFigure 7: Secondary Wiring System• Locking pul

Strany 118

Power-Zone® 4General and Application Information1911/2005© 2005 Schneider Electric All Rights ReservedRear Cable Compartment The rear cable compartme

Strany 119

20© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 General and Application InformationBus CompartmentThe bus compartment contains th

Strany 120

Power-Zone® 4General and Application Information2111/2005© 2005 Schneider Electric All Rights ReservedAuxiliary Instrument CompartmentsAuxiliary instr

Strany 121

22© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 General and Application InformationFigure 12: Circuit Breaker Lifter BarTraveling

Strany 122

Power-Zone® 4General and Application Information2311/2005© 2005 Schneider Electric All Rights ReservedFigure 14: Through-the-Door ConstructionHorizont

Strany 123

24© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 General and Application InformationInterrupting and Short-Time (Withstand) Capabi

Strany 124

Cutler-Hammer ProductsCutler-Hammer 5/15 kV Medium Voltage Switchgear Components4 9Type VCP-W Vacuum Circuit Breaker…A New Level of StandardizationAll

Strany 125

Power-Zone® 4General and Application Information2511/2005© 2005 Schneider Electric All Rights ReservedCircuit Breaker PartsThe Masterpact® NW circuit

Strany 126

26© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 General and Application InformationCircuit Breaker OperationPower-Zone 4 switchge

Strany 127 - Suggested Specifications

Power-Zone® 4General and Application Information2711/2005© 2005 Schneider Electric All Rights ReservedTwo-Step Stored Energy MechanismFigure 18: Charg

Strany 128

28© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 General and Application InformationCircuit Breaker and Equipment AccessoriesA num

Strany 129

Power-Zone® 4General and Application Information2911/2005© 2005 Schneider Electric All Rights ReservedMicrologic® Trip UnitsA new family of field-inst

Strany 130

30© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 General and Application InformationType P (Power Metering) Trip Unit Type H (Har

Strany 131

Power-Zone® 4General and Application Information3111/2005© 2005 Schneider Electric All Rights ReservedPowerlogic SystemPower-Zone 4 switchgear is avai

Strany 132

32© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 General and Application InformationSystem CommunicationsThe Powerlogic®, monitori

Strany 133

Power-Zone® 4General and Application Information3311/2005© 2005 Schneider Electric All Rights ReservedSystem ComponentsPowerlogic® system components a

Strany 134

34© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 General and Application InformationARC FLASH PROTECTION WITH MASTERPACT NW CIRCUI

Strany 135 - Schneider Electric Canada

Cutler-Hammer ProductsCutler-Hammer 5/15 kV Medium Voltage Switchgear Components4 9Type VCP-W Vacuum Circuit Breaker…A New Level of StandardizationAll

Strany 136 - Gain energy insight and

Power-Zone® 4General and Application Information3511/2005© 2005 Schneider Electric All Rights ReservedCalculating Arc Flash Incident energy using Mast

Strany 137 - Features

36© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 General and Application Information

Strany 138 - Applications

Power-Zone® 4Technical Overview3711/2005© 2005 Schneider Electric All Rights ReservedSECTION 3 : TECHNICAL OVERVIEWSECTION CONTENTS“Introduction” n .

Strany 139 - Front panel

38© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Technical OverviewINTRODUCTIONThis section contains basic technical information p

Strany 140 - Power quality

Power-Zone® 4Technical Overview3911/2005© 2005 Schneider Electric All Rights ReservedTable 1: Masterpact NW and NT Circuit Breaker Interrupting Rating

Strany 141 - Inputs and outputs

40© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Technical OverviewTable 2: Various Sensor Capacities of Masterpact NW and NT Circ

Strany 142 - Communications

Power-Zone® 4Technical Overview4111/2005© 2005 Schneider Electric All Rights ReservedKey Interlock OperationAs shown in the example below, a main-tie-

Strany 143 - ION7300 ION7330 ION7350

42© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Technical OverviewFunctionalityThe table below lists the standard and optional tr

Strany 144

Power-Zone® 4Technical Overview4311/2005© 2005 Schneider Electric All Rights ReservedTrip CurvesThis section contains typical characteristic trip curv

Strany 145 - Switch gives you the

44© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Technical OverviewFigure 23: Typical Micrologic 6.0 A/P/H Trip Units with Adjusta

Strany 146

Cutler-Hammer ProductsCutler-Hammer 5/15 kV Medium Voltage Switchgear Components8 5User-Friendly OperationType VCP-W Vacuum Circuit Breakercontrols an

Strany 147

Power-Zone® 4Technical Overview4511/2005© 2005 Schneider Electric All Rights ReservedFigure 24: Typical Micrologic 6.0 A/P/H Trip Units with Adjustabl

Strany 148 - ASCO POWERQUEST

46© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Technical OverviewFigure 25: Typical Micrologic 6.0 A/P/H Trip Units with Adjusta

Strany 149 - ASCO is the global leader in

Power-Zone® 4Technical Overview4711/2005© 2005 Schneider Electric All Rights ReservedFigure 26: Typical Micrologic 5.0/6.0 A/P/H Trip Units (Long-time

Strany 150 - Switch with Bypass-Isolation

48© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Technical OverviewFigure 27: Typical Micrologic 5.0/6.0 A/P/H Trip Units (Short-t

Strany 151 - 5200 Series Power Manager XP

Power-Zone® 4Technical Overview4911/2005© 2005 Schneider Electric All Rights ReservedFigure 28: Typical Micrologic 3.0 A Trip Unit (Long-time Pickup a

Strany 152 - Control Interfaces

50© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Technical OverviewFigure 29: Typical Micrologic 5.0/6.0 Trip Units (instantaneous

Strany 153 - Ensure continuous

Power-Zone® 4Technical Overview5111/2005© 2005 Schneider Electric All Rights ReservedFigure 30: Typical Micrologic 3.0 A Trip Unit (Instantaneous Pick

Strany 154 - LOAD MANAGEMENT SETTINGS

52© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Technical OverviewFigure 31: Typical Micrologic 2.0 A Trip Unit (Long-time Pickup

Strany 155 - Ordering Information

Power-Zone® 4Technical Overview5311/2005© 2005 Schneider Electric All Rights ReservedFigure 32: Micrologic 2.0/3.0/5.0/6.0 A/P/H Trip Unit Instantaneo

Strany 156 - 7000 Ser ies

54© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Technical OverviewSelection Tables with Transformer Ratings Transformer ratings f

Strany 157

Cutler-Hammer ProductsCutler-Hammer 5/15 kV Medium Voltage Switchgear Components8 5User-Friendly OperationType VCP-W Vacuum Circuit Breakercontrols an

Strany 158

Power-Zone® 4Technical Overview5511/2005© 2005 Schneider Electric All Rights Reserved240 V Three-Phase - 100% Motor Load / xd" = 25%b3005.0%72250

Strany 159

56© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Technical Overview480 V Three-Phase - 100% Motor Load / xd" = 25%b5005.0%601

Strany 160 - Galaxy PW

Power-Zone® 4Technical Overview5711/2005© 2005 Schneider Electric All Rights Reserved30005.75%360950000100000150000250000500000Unlimited30700412004660

Strany 161 - Galaxy PW Peripherals

58© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Technical Overview 600 V Three-Phase - 100% Motor Load / xd" = 25%b5005.0%48

Strany 162 - The Proven Solution

Power-Zone® 4Technical Overview5911/2005© 2005 Schneider Electric All Rights Reserved37505.75%360850000100000150000250000500000Unlimited27200380004370

Strany 163 - UPS Module Specifications

60© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Technical OverviewDistribution SystemsThis section contains a brief overview of W

Strany 164

Power-Zone® 4Technical Overview6111/2005© 2005 Schneider Electric All Rights ReservedDelta Grounded and Ungrounded SystemsFormerly common, Delta three

Strany 165

62© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Technical OverviewGround faults are an inadvertent flow of current between the no

Strany 166

Power-Zone® 4Technical Overview6311/2005© 2005 Schneider Electric All Rights ReservedResidual Ground Fault SensingResidual ground fault sensing system

Strany 167

64© 2005 Schneider Electric All Rights Reserved 11/2005Power-Zone® 4 Technical OverviewThe current sensor and ground fault interface module must be wi

Komentáře k této Příručce

Žádné komentáře