EN Switched Power Distribution Unit DK 7856.530 / 540 / 550 Assembly, Installation and Operation

Strany 2

Installing 6 10 Switched Power Distribution Unit EN 6 Installing Danger! Only trained specialists may perform the assembly and installation.

Strany 3 - Table of Contents 1

Operations 7 Switched Power Distribution Unit 11 EN 7 Operations 7.1 Interfaces The Switched PDU has two interfaces: the HTML interface accessed

Strany 4 - Documentation Notes 2

Operations 7 12 Switched Power Distribution Unit EN 7.2 HTML Interface The HTML interface is constructed of three major components: 1. System L

Strany 5 - Safety Instructions 3

Operations 7 Switched Power Distribution Unit 13 EN 7.2.1 Logging In Logging in through HTML requires directing the HTML client to the configured I

Strany 6

Operations 7 14 Switched Power Distribution Unit EN 7.2.3 Environmental Monitoring Sensors The Sensors page displays: • Temperature/humidity s

Strany 7 - Product Introduction 4

Operations 7 Switched Power Distribution Unit 15 EN Setting the system 3-phase load out-of-bound threshold: This setting to use for devices with 3-p

Strany 8

Operations 7 16 Switched Power Distribution Unit EN Enabling or disabling Telnet or SSH support: Select Enabled or Disabled from the appropriate

Strany 9 - Mounting 5

Operations 7 Switched Power Distribution Unit 17 EN • Optional –Both non-secure (HTTP) and SSL encrypted connections (HTTPS) are allowed access. •

Strany 10 - Installing 6

Operations 7 18 Switched Power Distribution Unit EN To add a new UPS: Select the UPS manufacturer type from the Type drop-down list, type an IP a

Strany 11 - Operations 7

Operations 7 Switched Power Distribution Unit 19 EN Adding and Deleting outlets from a group: Press the Edit link in the Action column for the assoc

Strany 12

2 Switched Power Distribution Unit Microsoft Windows is a registered trademark of Microsoft Corporatio

Strany 13

Operations 7 20 Switched Power Distribution Unit EN FTP The FTP configuration page is used for setup and maintenance of all settings required to

Strany 14

Operations 7 Switched Power Distribution Unit 21 EN Enabling or disabling SNMP support: Select Enabled or Disabled from the drop-down menu and press

Strany 15

Operations 7 22 Switched Power Distribution Unit EN Setting the search bind password for Distin-guished Name (DN): Enter the Search Bind Password

Strany 16

Operations 7 Switched Power Distribution Unit 23 EN Setting the TACACS+ server address: Enter the IP address or hostname in the Primary and/or Secon

Strany 17

Operations 7 24 Switched Power Distribution Unit EN Note! A restart of the PDU is required after activating new special features. 7.2.5 Tools

Strany 18

Operations 7 Switched Power Distribution Unit 25 EN When you enter a valid username and password, the command prompt (Switched PDU:) appears. If a l

Strany 19

Operations 7 26 Switched Power Distribution Unit EN Administrative Command Summary Add Grouptouser Grants a user access to one or more groups A

Strany 20

Operations 7 Switched Power Distribution Unit 27 EN Set System Area Specifies to total square feet for the system Set System Balance Specifies the

Strany 21

Operations 7 28 Switched Power Distribution Unit EN To display the names of commands that you may execute: At the command prompt, press Enter. A

Strany 22

Operations 7 Switched Power Distribution Unit 29 EN To display on/off status of one or more outlets: At the Switched PDU: prompt, type status, fol-l

Strany 23

Table of Contents 1 Switched Power Distribution Unit 3EN 1 Table of Contents 1 Table of Contents ...3 2 Documentation

Strany 24

Operations 7 30 Switched Power Distribution Unit EN Displaying accessible serial ports: The List Ports command displays accessible se-rial ports

Strany 25

Operations 7 Switched Power Distribution Unit 31 EN Ending a session: The Quit or Logout commands ends a session. A session ends automatically when

Strany 26

Operations 7 32 Switched Power Distribution Unit EN At the Verify Password: prompt, retype the new password and press Enter. Example The follo

Strany 27

Operations 7 Switched Power Distribution Unit 33 EN Examples The following commands grant the user JaneDoe access to outlets A1 and Webserver_1: Sw

Strany 28

Operations 7 34 Switched Power Distribution Unit EN Outlet Administration Setting the sequencing interval: The Set Outlet SeqInterval commands se

Strany 29

Operations 7 Switched Power Distribution Unit 35 EN Example The following command displays all outlet infor-mation: Switched PDU: show outlets<E

Strany 30

Operations 7 36 Switched Power Distribution Unit EN Tower Administration Creating a descriptive tower name: The Set Tower Name command assigns a

Strany 31

Operations 7 Switched Power Distribution Unit 37 EN Example Switched PDU: show towers<Enter> Tower ID: .A Name:

Strany 32

Operations 7 38 Switched Power Distribution Unit EN To create an Environmental Monitor name: At the Switched PDU: prompt, type set envmon name fo

Strany 33

Operations 7 Switched Power Distribution Unit 39 EN To set the serial port timeout value: At the Switched PDU: prompt, type set port timeout, follow

Strany 34

Documentation Notes 2 4 Switched Power Distribution Unit EN 2 Documentation Notes The audience for this guide is the technical spe-cialist fami

Strany 35

Operations 7 40 Switched Power Distribution Unit EN Setting the system input power factor: The Set System PF command is used to set the input pow

Strany 36

Operations 7 Switched Power Distribution Unit 41 EN To enable or disable strong passwords: At the Switched PDU: prompt, type set option strong passw

Strany 37

Operations 7 42 Switched Power Distribution Unit EN Setting the IP address: The Set Ipaddress command sets the TCP/IP address of the network inte

Strany 38

Operations 7 Switched Power Distribution Unit 43 EN HTTP Administration Note! A restart is required after setting or changing ANY Telnet/Web confi

Strany 39

Operations 7 44 Switched Power Distribution Unit EN Examples The following command sets the FTP host IP address to 12.34.56.99: Switched PDU: se

Strany 40

Operations 7 Switched Power Distribution Unit 45 EN Example The following command sets the automatic up-date day to Sunday: Switched PDU: set ftp a

Strany 41

Operations 7 46 Switched Power Distribution Unit EN To set the local GMT offset: At the Switched PDU: prompt, type set sntp gmtoffset, followed

Strany 42

Operations 7 Switched Power Distribution Unit 47 EN Example The following command changes UPS type for the record at index number 2 to ‘MGE’: Switc

Strany 43

Operations 7 48 Switched Power Distribution Unit EN Enabling/disabling UPS voltage polling: With a UPS record configured, the PDU by default enab

Strany 44

Advanced Operations 8 Switched Power Distribution Unit 49 EN 8 Advanced Operations 8.1 SSL Secure Socket Layers (SSL) version 3 enables secure H

Strany 45

Safety Instructions 3 Switched Power Distribution Unit 5EN 3.1 Safety Precautions This section contains important safety and regulatory informat

Strany 46

Advanced Operations 8 50 Switched Power Distribution Unit EN SSH Command Summary Command Description Set SSH Enables/disables SSH support Set

Strany 47

Advanced Operations 8 Switched Power Distribution Unit 51 EN SNMP Command Summary Command Description Set SNMP Enables or disables SNMP sup-port S

Strany 48

Advanced Operations 8 52 Switched Power Distribution Unit EN To set the Getcomm community string: At the Switched PDU: prompt, type set snmp getc

Strany 49 - Advanced Operations 8

Advanced Operations 8 Switched Power Distribution Unit 53 EN All traps include the Location of the PDU as defined with the Set Location command. S

Strany 50

Advanced Operations 8 54 Switched Power Distribution Unit EN Set Trap Infeed HighThresh Sets the Infeed Load trap high limit Set Trap Outlet Cha

Strany 51

Advanced Operations 8 Switched Power Distribution Unit 55 EN Enabling or Disabling a Status trap: The Set Trap … Status command is used to en-able o

Strany 52

Advanced Operations 8 56 Switched Power Distribution Unit EN Displaying trap configuration information: The Show Traps command displays informati

Strany 53

Advanced Operations 8 Switched Power Distribution Unit 57 EN LDAP Command Summary Command Description Add GrouptoLDAP Grants an LDAP group ac-cess

Strany 54

Advanced Operations 8 58 Switched Power Distribution Unit EN To set the LDAP host address: At the Switched PDU: prompt, type set ldap, followed b

Strany 55

Advanced Operations 8 Switched Power Distribution Unit 59 EN Search Bind DN. Maximum password size is 20 characters. To set the Bind Password DN:

Strany 56

Safety Instructions 3 6 Switched Power Distribution Unit EN 3.2 Life-Support Policy As a general policy, Rittal does not recommend the use of a

Strany 57

Advanced Operations 8 60 Switched Power Distribution Unit EN Note! With the Remote Only method, if au-thentication fails due to a communica-tion

Strany 58

Advanced Operations 8 Switched Power Distribution Unit 61 EN Example The following command verifies the DNS configu-ration: Switched PDU: ping rit

Strany 59

Advanced Operations 8 62 Switched Power Distribution Unit EN Example The following command displays all LDAP groups with their access privilege l

Strany 60

Advanced Operations 8 Switched Power Distribution Unit 63 EN Displaying LDAP Group access: The List LDAPGroup command displays all ac-cess rights fo

Strany 61

Advanced Operations 8 64 Switched Power Distribution Unit EN 8.4.2 LDAP Technical Specifications LDAP Authentication Process Simple Bi

Strany 62

Advanced Operations 8 Switched Power Distribution Unit 65 EN 8.4.3 LDAPS Client Specifications Secure Sockets Layer (SSL) version 3 Transport Layer

Strany 63

Advanced Operations 8 66 Switched Power Distribution Unit EN To enable or disable TACACS+ support: At the Switched PDU: prompt, type set tacacs,

Strany 64

Advanced Operations 8 Switched Power Distribution Unit 67 EN Note! Rittal recommends NOT setting the au-thentication order to Remote Only until the

Strany 65

Advanced Operations 8 68 Switched Power Distribution Unit EN all outlets, you must use multiple Add OutletTo-TACACS commands. To grant outlet a

Strany 66

Advanced Operations 8 Switched Power Distribution Unit 69 EN Example The following command displays information about the TACACS+ account 1: Switche

Strany 67

Product Introduction 4 Switched Power Distribution Unit 7EN 4 Product Introduction The Switched Power Distributing Unit (Switched PDU) is a compac

Strany 68

Advanced Operations 8 70 Switched Power Distribution Unit EN Syslog The PDU’s Syslog support is RFC3164-compliant and enables off-PDU viewing and

Strany 69

Advanced Operations 8 Switched Power Distribution Unit 71 EN Setting the SMTP server address: The Set Email Host command sets the IP address or host

Strany 70

Advanced Operations 8 72 Switched Power Distribution Unit EN Displaying Email configuration information: The Show Email command displays Email co

Strany 71

Appendices 9 Switched Power Distribution Unit 73 EN Upload/Download Process GETting a configuration file (Download): 1. Open the FTP client. In a

Strany 72

Technical Specifications 10 74 Switched Power Distribution Unit EN To reset to factory defaults, except network settings From the HTML interface

Strany 73 - Appendices 9

Technical Specifications 10 Switched Power Distribution Unit 75 EN 10.2 Data Connections RS-232 port Switched PDUs are equipped standard with an RJ

Strany 74 - 10 Technical Specifications

Technical Specifications 10 76 Switched Power Distribution Unit EN 10.4 Regulatory Compliance Product Safety Units have been safety tested and c

Strany 75 - 67 543218

Maintenance and Cleaning 11 Switched Power Distribution Unit 77 EN 11 Maintenance and Cleaning The Rittal Switched Power Distribution Unit is a ma

Strany 76 - 10.4 Regulatory Compliance

Product Introduction 4 8 Switched Power Distribution Unit EN 4.2 Power Supply The Switched PDU is powered with the included Connection Plug. Th

Strany 77 - 12 Customer Service

Mounting 5 Switched Power Distribution Unit 9EN 5 Mounting The included installation set allows the mounting of the unit on the cabinet frame and