www.mgeups.com Galaxy 5000 20 to 120 kVA Technical specifications THE UNINTERRUPTIBLE POWER PROVIDER
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 10 Characteristics The Galaxy 5000 charger can handle backup times
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 11 the section on battery protection). For batteries on racks, it is
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 12 (excessive discharge) when the percent load is low. This is becaus
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 13 inverter uses sixpack IGBT modules (capacitive half bridge, not is
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 14 Free-frequency chopping The regulation system for the output volta
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 15 Imbalanced conditions For a 100% load imbalance, shift remains le
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 16 Direct thermal monitoring of the sixpack IGBT modules A sensor pl
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 17 Bypass AC source tolerances and transfer conditions When the bypas
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 18 kVA bypass is housed in an enclosure and the 360 and 600 kVA versi
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 19 Low-battery warning. General alarm. Battery fault. 2.9 Comm
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 2 Contents 1. Presentation...
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 20 3. Parallel connection The modular design of Galaxy 5000 enables
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 21 NormalAC inputLoadBypassAC input P1(kVA)P1(kVA) P1(kVA)ASI3R
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 22 4. Functions Main standard functions Double-conversion topolog
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 23 UPS cabinet without battery (in separate cabinet) - width 710 mm
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 24 > 250 mm710 mm> 1000 mm Fig. 21. No major constraints on
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 25 Battery Type Sealed lead-acid or optional vented lead-acid or nic
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 26 Communication Power rating Pn (kVA at PF = 0.8) (rated output appa
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 27 Physical characteristics - environment and standards Power rating
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 28 Current and protection characteristics Power rating Pn (kVA at PF
MGE UPS SYSTEMS 140 avenue Jean-Kuntzmann Zirst Montbonnot Saint-Martin 38334 SA
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 3 1. Presentation 1.1 Galaxy 5000 range Optimised power protection
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 4 networks and the web make for proactive maintenance that enhances t
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 5 Optimised protection for applications such as data centres, telecom
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 6 Flexibility Galaxy 5000 can meet the upgrade needs of sites, in te
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 7 2. Technical specifications 2.1 Operating principle Purpose These
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 8 LoadRectifier/chargerBatteryInverterStaticbypassMaintenancebypassNo
Galaxy 5000 technical specifications MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page 9 AC InputSixpackcomponent Input rectifier Sixpacki1U1U2U3TDi2i3Vout